Ampacity refers to the maximum current (measured in amperes or simply amps) that an insulated conductor can safely carry without exceeding its insulation and jacket temperature limitations. As current flows through a conductor, it generates heat. This heat must dissipate into the environment; otherwise, the cable’s temperature would rise above safe operating limits, leading to deterioration and potential failure.
The ampacity of a cable should equal or exceed the maximum current it will carry during its service life without surpassing its temperature rating. The temperature rating depends on the heat resistance of the insulation and jacket materials. Common conductor temperature ratings include 90°C, 150°C and 200°C, but some special-purpose wires can handle temperatures as high as 1,200°C1.
Ampacity Chart for Copper Conductors
Wire Gauge Size |
60°C (140°F) |
75°C (167°F) |
90°C (194°F) |
14 AWG |
15 A |
20 A |
25 A |
12 AWG |
20 A |
25 A |
30 A |
10 AWG |
30 A |
35 A |
40 A |
8 AWG |
40 A |
50 A |
55 A |
6 AWG |
55 A |
65 A |
75 A |
4 AWG |
70 A |
85 A |
95 A |
3 AWG |
85 A |
100 A |
115 A |
2 AWG |
95 A |
115 A |
130 A |
1 AWG |
— |
130 A |
145 A |
1/0 AWG |
— |
150 A |
170 A |
2/0 AWG |
— |
175 A |
195 A |
3/0 AWG |
— |
200 A |
225 A |
4/0 AWG |
— |
230 A |
260 A |
250 kcmil |
— |
255 A |
290 A |
300 kcmil |
— |
285 A |
320 A |
350 kcmil |
— |
310 A |
350 A |
500 kcmil |
— |
380 A |
430 A |
600 kcmil |
— |
420 A |
475 A |
750 kcmil |
— |
475 A |
535 A |
1000 kcmil |
— |
545 A |
615 A |
Several factors impact ampacity, including ambient temperatures and the number of current-carrying conductors. Here are key considerations:
To take this a step further, assume the ambient temperature of this application is 47°C. Using the Ambient Temperature Correction Factors from NEC Table 310.15(B)(1)(1), a correction factor of 0.82 is applied, reducing the ampacity to 7.38 amps.
Minimum Circuit Ampacity (MCA) refers to the minimum size a conductor (wire) must be to safely handle the amount of current (amperes) drawn by electrical equipment. It’s essential to ensure that the conductors can handle the load without overheating. However, it’s important to note that MCA represents the minimum capacity required, not necessarily the actual current that will flow through the equipment. When sizing conductors based on MCA, we ensure that they can handle the specified current without exceeding their ampacity.
For example, if an HVAC unit has an MCA of 14.9 amps, using 14-gauge copper wire would be sufficient. If the MCA is 15.1 amps, we’d increase to 12-gauge wire. Always check the equipment’s nameplate for the MCA value and select conductors accordingly to avoid oversizing
Conclusion
In industrial applications, ampacity impacts wire sizing, equipment selection, and adherence to electrical codes. By understanding ampacity, engineers, and electricians can design robust systems that withstand the demands of heavy machinery and high voltages. So, next time you select cables for an industrial project, keep ampacity in mind—it’s the lifeline of your electrical infrastructure!