Ampacity and Its Impact on Industrial Cable Selection

Posted by ATPC Team on June 25, 2024


amps graphic 2 (002)-1Ampacity is crucial in industrial wiring to ensure safe and efficient electrical systems. Let’s explore what ampacity is, how it affects cable selection, and why it matters in industrial settings. 

What Is Ampacity? 

Ampacity refers to the maximum current (measured in amperes or simply amps) that an insulated conductor can safely carry without exceeding its insulation and jacket temperature limitations. As current flows through a conductor, it generates heat. This heat must dissipate into the environment; otherwise, the cable’s temperature would rise above safe operating limits, leading to deterioration and potential failure.  

heat-icon

Temperature Ratings 

The ampacity of a cable should equal or exceed the maximum current it will carry during its service life without surpassing its temperature rating. The temperature rating depends on the heat resistance of the insulation and jacket materials. Common conductor temperature ratings include 90°C, 150°C and 200°C, but some special-purpose wires can handle temperatures as high as 1,200°C1.

Ampacity Chart for Copper Conductors 

 

Wire Gauge Size 

60°C (140°F) 

75°C (167°F) 

90°C (194°F) 

14 AWG 

15 A 

20 A 

25 A 

12 AWG 

20 A 

25 A 

30 A 

10 AWG 

30 A 

35 A 

40 A 

8 AWG 

40 A 

50 A 

55 A 

6 AWG 

55 A 

65 A 

75 A 

4 AWG 

70 A 

85 A 

95 A 

3 AWG 

85 A 

100 A 

115 A 

2 AWG 

95 A 

115 A 

130 A 

1 AWG 

 

130 A 

145 A 

1/0 AWG 

 

150 A 

170 A 

2/0 AWG 

 

175 A 

195 A 

3/0 AWG 

 

200 A 

225 A 

4/0 AWG 

 

230 A 

260 A 

250 kcmil 

 

255 A 

290 A 

300 kcmil 

 

285 A 

320 A 

350 kcmil 

 

310 A 

350 A 

500 kcmil 

 

380 A 

430 A 

600 kcmil 

 

420 A 

475 A 

750 kcmil 

 

475 A 

535 A 

1000 kcmil 

 

545 A 

615 A 

Derating Factors 

Several factors impact ampacity, including ambient temperatures and the number of current-carrying conductors. Here are key considerations: 

  1. Ambient Temperature: The rate at which heat dissipates depends on the installation environment. Heat radiates out of the cable less effectively as the ambient temperature rises. To ensure we do not exceed the cable's temperature rating, a correction factor is applied to the ampacity rating. As the ambient temperature rises, correction factors reduce the cable ampacity value. 
  1. Number of Conductors: More conductors in an enclosed space can lead to a higher ambient temperature environment. Derating compensates for this increase in heat. If more than three current-carrying conductors are in a raceway or cable, the ampacity ratings must be derated according to NEC requirements. 
Industrial Example 

Close-up image of half-cut wires revealing internal conductors, illustrating the structure and composition of electrical wiring.An industrial automation application requires a 12 conductor, 16 AWG control cable. The chosen cable has a maximum conductor temperature rating of 90°C. Using NEC Table 310.16, the allowable ampacity for a 16 AWG cable with three current-carrying conductors is 18 amps. However, the cable for this application uses 12 conductors, which requires the application of a correction factor per NEC Table 310.15(C)(1) of 0.50, reducing the allowable ampacity to 9 amps.  

To take this a step further, assume the ambient temperature of this application is 47°C. Using the Ambient Temperature Correction Factors from NEC Table 310.15(B)(1)(1), a correction factor of 0.82 is applied, reducing the ampacity to 7.38 amps. 

 

F.A.Q - What is the minimum circuit ampacity?  

 

Minimum Circuit Ampacity (MCA) refers to the minimum size a conductor (wire) must be to safely handle the amount of current (amperes) drawn by electrical equipment. It’s essential to ensure that the conductors can handle the load without overheating. However, it’s important to note that MCA represents the minimum capacity required, not necessarily the actual current that will flow through the equipment. When sizing conductors based on MCA, we ensure that they can handle the specified current without exceeding their ampacity. 

For example, if an HVAC unit has an MCA of 14.9 amps, using 14-gauge copper wire would be sufficient. If the MCA is 15.1 amps, we’d increase to 12-gauge wire. Always check the equipment’s nameplate for the MCA value and select conductors accordingly to avoid oversizing 

 

Conclusion 

In industrial applications, ampacity impacts wire sizing, equipment selection, and adherence to electrical codes. By understanding ampacity, engineers, and electricians can design robust systems that withstand the demands of heavy machinery and high voltages. So, next time you select cables for an industrial project, keep ampacity in mind—it’s the lifeline of your electrical infrastructure!  